Double-T floor units in prestressed concrete have a ribbed cross-section and a smooth under face. The units are mainly used for greater spans and imposed loading. The units are manufactured with two standard widths: 2400 and 3000 mm. However, the units can also be manufactured in a smaller width to meet the requirements of a particular project. The minimum width is 1500 mm. The standard profile is given below.
The ends of the units can be notched to reduce the overall structural depth. A structural topping can be used to ensure both vertical shear transfer between adjacent units and horizontal diaphragm action in the floor plate. The standard double-T units have a minimum fire resistance of 60 to 120 minutes. Anchor rails can be cast into the soffits of the webs.
Characteristics TT-2400
Profile | h mm | b mm | b1 mm | b2 mm | b0 mm | Weight kg / m2 |
Fire resistence 60 min | 500 | 2390 | 1068 | 661 | 120 | 261 |
Fire resistence 90 min | 500 | 2390 | 1084 | 671 | 150 | 287 |
Fire resistence 120 min | 500 | 2390 | 1100 | 645 | 200 | 332 |
Characteristics TT-3000
Profile | h mm | b mm | b1 mm | b2 mm | b0 mm | Weight kg / m2 |
Fire resistence 60 min | 500 | 2990 | 1368 | 811 | 120 | 232 |
Fire resistence 90 min | 500 | 2990 | 1384 | 821 | 150 | 254 |
Fire resistence 120 min | 500 | 2990 | 1400 | 795 | 200 | 290 |
The performance curves give the variance of load bearing capacity dependently on the span length.
Connections between TT floors and supporting beams are made through lapping reinforcement in the structural topping or by bars welded to plates fully anchored in the units. There is possible connection placed below.
Connection through structural topping
Connections between TT floors and supporting beams are made through lapping reinforcement in the structural topping or by bars welded to plates fully anchored in the units. There is possible connection placed below.
Conncetions between adjacent units
Welded adjacment
Holes may be formed in double-T slabs in the positions shown in the figure. The maximum dimensions are given in the table.
l / b | TT - 2400 | TT - 3000 |
Center | 1000 / 630 | 1000 / 930 |
Edge | 1000 / 320 | 1000 / 460 |
Corner | 1000 / 320 | 1000 / 460 |
The TT-units should always be stacked one above the other and the soft wood bearers placed at the slab ends should also be one above the other. This also applies when loading on the truck.
The units are provided with four cast-in lifting hooks, each over the line of the webs. The slings or chains should be long enough to enable an inclination to the slab of not less than 600.